EVK-F5-4NHS2-2NHS00-LM-ÜA
Protection class II, for alternating current 50Hz, rated operating voltage AC 400V,
made of glass fibre reinforced polyester, colour: RAL 7035
Outer door with swivelling lever lock for a half cylinder lock (total length 45 mm)
with the following fittings:
01 x busbar system 5-pole, 185mm, Cu 50x10mm, 600A, incl. PEN bracket
02 x NH switch-disconnector 3-pole, size 2, 400A, V connection 35-240mm² (supply)
+ Connection set for parallel connection
03 x current transformer 600/5A, accuracy class 0.5
03 x NH switch-disconnector 3-pole, size 2, 400A, V connection 35-240mm² (outgoing circuit)
01 x D02 fuse switch-disconnector, 3-pole, 63A (back-up fuse ÜA)
01 x surge arrester 3-pole, type 2
01 x Evilon pipe mounted on the side for cable routing upwards
Installations above:
01 x D02 fuse switch-disconnector, 3-pole, 6A (voltage path fuse)
01 x Measurement disconnect terminals consisting of current path, voltage path
Can be replaced by CLEMAP three-phase meter
01 x D02 fuse switch-disconnector, 1-pole, 20A (back-up fuse FI/LS)
01 x FI/LS 1+N, C 16A, 30mA
01 x 24V, 1.3A power supply unit
01 x distribution terminals for 24V
01 x switch 8 ports // Digitus, operating temperature -30 - 80°C
incl. plastic contact protection cover, foam insert
and equipotential bonding bar PAS 100
Weight | 58 kg / Stk. |
---|
WGR | 2 |
---|