EVK-F5-2VL240-3NHS2-1NHS00-
Protection class II, for alternating current 50Hz, rated operating voltage AC 400V,
made of glass fibre reinforced polyester, colour: RAL 7035
Outer door with swivelling lever lock for a half cylinder lock (total length 40 mm)
with the following fittings:
01 x busbar system 5-pole, 185mm, Cu 50x10mm, 600A, incl. PEN bracket
02 x V-Anspeiseklemmen 5x 35-240mm²
01 x Einbauplatz Stromwandler
03 x NH-Lastschaltleiste 3-polig, Gr.2, 400A, V-Anschluss 35-240mm² (Anspeisung)
01 x NH-Lastschaltleiste 3-polig, Gr.00, 160A, V-Anschluss 10-70mm² (Reserve)
01 x NH switch-disconnector 3-pole, size 00, 160A, V-connection 10-70mm²
(Vorsicherung ÜA inkl. 63A Sicherung)
01 x Blitzstrom-Kombiableiter 3-polig+1, Typ 1+2, BKIII+IV
01 x Evilon pipe mounted on the side for cable routing upwards
Installations above:
01 x Gerätetragschiene
incl. plastic contact protection cover, foam insert
and equipotential bonding bar PAS 100
| Weight | 58 kg / Stk. |
|---|
| WGR | 2 |
|---|