EVK-F5-2VL240-3NHS2-1NHS00-
Protection class II, for alternating current 50Hz, rated operating voltage AC 400V,
made of glass fibre reinforced polyester, colour: RAL 7035
Outer door with swivelling lever lock for a half cylinder lock (total length 40 mm)
with the following fittings:
01 x busbar system 5-pole, 185mm, Cu 50x10mm, 600A, incl. PEN bracket
02 x V supply terminals 5x 35-240mm²
01 x installation space for separable current transformers
03 x NH switch-disconnector 3-pole, size 2, 400A, V connection 35-240mm² (supply)
01 x NH switch-disconnector 3-pole, size 00, 160A, V-connection 10-70mm² (reserve)
01 x NH switch-disconnector 3-pole, size 00, 160A, V-connection 10-70mm²
(back-up fuse ÜA incl. 63A fuse)
01 x lightning current combined arrester 3-pole+1, type 1+2, BKIII
01 x Evilon pipe mounted on the side for cable routing upwards
Installations above:
01 x Device support rail
01 x D02 fuse switch-disconnector, 3-pole, 6A (voltage path fuse)
01 x installation space for LoadManagement
01 x D02 fuse switch-disconnector, 1-pole, 6A (back-up fuse for power supply unit / measuring device / LoadManagment)
01 x distribution terminals L / N / PE
01 x 24V, 1.3A power supply unit
01 x switch 8 ports // WAGO, operating temperature -30 - 80°C
incl. plastic contact protection cover, foam insert
and equipotential bonding bar PAS 100
| Weight | 58 kg / Stk. |
|---|
| WGR | 2 |
|---|