EVK-F4-1NHS2-2NHS2-LM-ÜA
Protection class II, for alternating current 50Hz, rated operating voltage AC 400V,
made of glass fibre reinforced polyester, colour: RAL 7035
Outer door with swivelling lever lock for a half cylinder lock (total length 40 mm)
with the following fittings:
01 x busbar system 5-pole, 185mm, Cu 40x10mm, 400A, incl. PEN bracket
01 x NH switch-disconnector 3-pole, size 2, 400A, V-connection 35-240mm² (supply)
03 x current transformer 400/5A, accuracy class 1
02 x NH switch-disconnector 3-pole, size 2, 400A, V-connection 35-240mm² (outgoing circuit)
01 x D02 fuse switch-disconnector, 3-pole, 63A (back-up fuse ÜA)
01 x 3-pole lightning current combined arrester, type 1+2
01 x Evilon pipe mounted on the side for cable routing upwards
Installations above:
01 x D02 fuse switch-disconnector, 3-pole, 6A (voltage path fuse)
01 x Measurement disconnect terminals consisting of current path
01 x Installation space for "LoadManagement" or three-phase meter
01 x D02 fuse switch-disconnector, 1-pole, 10A
01 x 24V, 1.3A power supply unit
01 x switch 8 ports // Digitus, operating temperature -30 - 80°C
incl. plastic contact protection cover, foam insert
and equipotential bonding bar PAS 100
Weight | 58 kg / Stk. |
---|
WGR | 2 |
---|